Line 410: | Line 410: | ||
[[File:6_8_5_2.png|center]] | [[File:6_8_5_2.png|center]] | ||
− | + | A response string, during data exchange between the devices will look like: | |
<- '''20 03 02 00 10 C6 A0''' | <- '''20 03 02 00 10 C6 A0''' | ||
− | + | Responding device address: 0x20 (b0 byte of UART1 transmit data register b1:b0). | |
− | + | Function: 0x03 - the result of reading the values from several holding registers (b1 byte of UART1 transmit data register b1:b0). | |
− | + | The number of returned bytes: 0x02 (b2 byte of UART1 transmit data register b3:b2). | |
− | + | The value of the high byte of the requested register: 0x00 (b3 byte of UART1 transmit data register b3:b2). | |
− | + | The value of the least significant bit of the requested register: 0x10 (b4 byte of UART1 transmit data register b5:b4). | |
− | + | Check sum: 0xC6A0 (b5 byte of UART1 transmit data register b5:b4 and b6 byte of UART1 transmit data register b7:b6 respectively — driver adds automatically). | |
== See also == | == See also == |
Revision as of 14:55, 11 September 2016
Contents
General description
Two of eleven IO channels (#9 and #10) CANNY 7 supports UART, RS-232 serial protocols data transmission/reception. It may be used to connect the controllers with each other or with external equipment supporting this communications protocols. The channels may be activated independently of each other and have individual data speed setting, protocol type and configuration, pull up line.
UART implementation in CANNY 7 controllers allows to organize serial data reception and transmission over a single wire in half-duplex mode. Thus CANNY7 may have two independent connections using the UART protocol. Monitoring of the data link status should be done from the functional diagram. If the channel is free, the device may start data transmitting , otherwise the device should wait for the line release.
RS-232 implementation by using both UART data channels , allows to exchange data with other RS-232 device in a duplex mode, i.e. one channel to perform data sending and on the other to simultaneously receive data.
Modbus protocol in CANNY7 controllers implemented as over UART as over RS-232. As ADU (Application Data Unit) used compact binary option Modbus RTU. Checking the data integrity carried out by automatically calculated checksum (CRC). Package size is limited to 16 bytes including the CRC.
Note: | For correct operation of all protocols based on the UART / RS-232 requires that all GND terminals of the devices committing communication, were given to a single potential ("common ground"). |
Note: | In UART implementation-active line is the potential GND 100mA, passive - positive potential of a given internal or external channel pull-up. In implementing RS-232 - the potentials inverse. |
Driver UART/RS-232/Modbus operates using controllers' channels resources, but has a higher priority than a discrete input-output driver. Thus, upon activation of UART/RS-232/Modbus driver, for channels involved in its operation, a value changes in registers associated with discrete input-output driver, will be ignored.
Driver registers
The following describes the acceptable and returnable values of the driver control operation registers.
UART / RS-232 / Modbus Driver Configuration Registers.
Address | Expected values | ||||||||
---|---|---|---|---|---|---|---|---|---|
|
| ||||||||
|
|
UART driver configuration is determined by the constants that represent the combination of parameters that determine the speed, mode, additional date transmission parameters and line potential in the passive mode.
Parameter | Acceptable values |
---|---|
The data rate, bps | 110; 150; 300; 600; 1200; 1800; 2400; 4800; 9600; 19200; 38400; 57600 |
Mode | UART; RS-232 |
Pull-up in UART mode | plus; air |
The transfer direction in RS-232 mode | receive; transmit |
Data bits | 8; 9 |
parity | N (no) ; O (odd) ; E (even) |
Number of stop bits | 1; 2 |
Named constants that represent UART configuration parameters combination, available to the user in the "UART / RS-232 modes" CannyLab constants directory, which can be accessed via function block entry context menu having "constant" type.
UART / RS-232 / Modbus Diagnostic Registers.
Address | Return values | ||||||||
---|---|---|---|---|---|---|---|---|---|
|
| ||||||||
|
| ||||||||
|
|
UART / RS-232 / Modbus Receive Registers.
Address | Expected values | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
|
| |||||||||
|
| |||||||||
|
| |||||||||
|
| |||||||||
|
|
UART / RS-232 / Modbus Transmit Registers.
Address | Expected values | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
|
| |||||||||
|
| |||||||||
|
| |||||||||
|
|
Controller operation in UART mode
Operating in UART mode, the controller can perform half-duplex data transmission/reception on a single wire.
An example of a functional diagram for receiving data by UART.
An example of a functional diagram for transmitting data by UART.
Note: | Particular attention should be paid to the fact that in order to avoid collisions while sending data, it is necessary to strictly control UART channel data ready to send buffer: if the buffer is not ready, then at the moment the driver is receiving data, sending data should be postponed. |
Controller operation in RS-232 mode
Operating on the RS-232 protocol controller can use each of its data transfer channels only in simplex (unidirectional) mode. When using both UART channels, which operates independently of each other, it is possible to organize a full-duplex mode of data transmission via two wires: one channel - only reception, the second - the only transmission.
An example of a functional diagram working with RS-232. Receiving data through UART2, provided that the value of bytes b1: b0 is "0hAAAA", the controller sends, via UART1, 2 bytes of data containing the value «0xBBBB».
Modbus RTU implementation
UART/RS-232 driver includes functionality automatically create and verify the checksum using the Modbus RTU standard, which simplifies controller inclusion to the network operating under this protocol. Manage checksum formation for messages to be transmitted and its verification at reception is possible through the appropriate driver registers.
Note: | When operating in Modbus mode, UARTx received data length register, contains the value concidering received checksum byte (CRC), those 2 bytes greater than the length of the payload of the message. When sending a Modbus packet, UARTx transmit data length register value must also be increased by 2 bytes to accommodate and transfer CRC. |
An example of a functional diagram of controller operating in Modbus MASTER-node mode over RS-232. Performing the diagram, the controller periodically sends to SLAVE-node with address 0x20 a request to receive from it the value of the Modbus-data register with address 0x0001. Getting an answer to its request, the MASTER accompanies with short blinking of green LED.
A query string, when communicating between these devices will look like: -> 20 03 00 01 00 01 D3 7B
Polled device address: 0x20 (b0 byte of UART2 receive data register b1:b0).
Function: 0x03 - reading values from multiple holding registers (b1 byte of UART2 receive data register b1:b0).
Number of the first requested register: 0x0001 (b2 and b3 bytes of UART2 receive data register b3:b2).
Number of requested registers: 0x0001 (b4 and b5 bytes of UART2 receive data register b5:b4).
Check sum: 0xD37B (b6 and b7 bytes of UART2 receive data register b7:b6 — driver adds automatically).
An example of a functional diagram of controller operating in Modbus SLAVE-node mode over RS-232. Receiving a request for data transmission from MASTER, the controller sends back the requested register state. Controller transmits 2 byte of data (+2 CRC bytes), as Modbus registers are 16 bits.
A response string, during data exchange between the devices will look like:
<- 20 03 02 00 10 C6 A0
Responding device address: 0x20 (b0 byte of UART1 transmit data register b1:b0).
Function: 0x03 - the result of reading the values from several holding registers (b1 byte of UART1 transmit data register b1:b0).
The number of returned bytes: 0x02 (b2 byte of UART1 transmit data register b3:b2).
The value of the high byte of the requested register: 0x00 (b3 byte of UART1 transmit data register b3:b2).
The value of the least significant bit of the requested register: 0x10 (b4 byte of UART1 transmit data register b5:b4).
Check sum: 0xC6A0 (b5 byte of UART1 transmit data register b5:b4 and b6 byte of UART1 transmit data register b7:b6 respectively — driver adds automatically).